PRODUCT APPLICATION
Main insulation restoration of 600v-35kv solid dielectric cable: When stress cone is made on solid dielectric cable up to 35kV, it is the main insulation: Jacket restoration of intermediate joint and terminal; Moisture-proof seals for electrical connections:Businsulation: Cableend seal, When wrapping, stretch the tape so that it is 3/4 of the width before stretching.Wrapped PVC electrical tape outside to provide mechanical protection.
PRODUCT Technical indicators
|
SPECIFICATIONS: XF-J30(S-28) |
|||
|
PROPERTY |
VALUE |
UNIT |
TEST METHOD |
|
Physical property |
|||
| Tensile strength | ≥1.3 | Mpa | GB/T 528 |
| Elongation at break | ≥500 | % | GB/T 528 |
| Dielectric Strength | ≥20 | kV/mm | GB/T 1695 |
| Volume Resistivity | ≥1x10⁴ | Ω·cm | GB/T 1692 |
| Dielectric loss tangent | ≤0.05 | --- | GB/T 1693 |
| Dielectric Constant | ≤5.0 | --- | GB/T 1693 |
| Self viscosity | No loosening | --- | JB/T 6468 |
| Heat-resistant stress cracking | No cracking | --- | JB/T 6468 |
| Heat Resistance | 100 | ℃ | JB/T 6468 |
| Data in the table represent average test results and are not to be used for specification purposes. The product user should make his l her own tests to determine the product.it's suitable for the intended use. | |||
PRODUCT General specifications
| STANDARD SIZES: | ||
|
Width |
Length |
Thickness |
|
19mm |
9.1m | 0.76mm |
| 25mm | 5m | 0.76mm |
| 38mm | 9.1m | 0.76mm |
| 50mm | 9.1m | 0.76mm |
| Other sizes and cores are available. Contact factory | ||
PRODUCT PACKAGE