PRODUCT APPLICATION
• Used for cable fire prevention, to strengthen the fireproof performance of cable sheath;
• Suitable for additional insulation and cable parts prone to failure where there are fire hazards;
• Suitable for high and low-voltage power supply lines, especially fire retardant engineering of cables laid under environmental conditions such as channel, tunnel, and overhead in power plants, substations, iron and steel, chemical industry, construction, subways, mines, and ships;
• Applicable to all forms of fire spreading, effectively isolating fire spreading.
PRODUCT Technical indicators
SPECIFICATIONS: X-FHD-108 |
|||
PROPERTY |
VALUE |
UNIT |
TEST METHOD |
Physical property |
|||
Tensile strength | ≥3 | MPa | GB/T 528-2009 |
Elongation at break | ≥500 | MPa | GB/T 528-2009 |
Tensile strength change rate | ≤±20% | --- | GB/T2951.12-2008 |
Change rate of elongation at break | ≤±20% | --- | GB/T 2951.12-2008 |
Water resistance | Immersion for 15 days, no bubbles, wrinkling delamination, cracking, and other phenomena | — | Ga478-2004 |
Acid resistance, alkali resistance, Salt tolerance | Immersion for 7 days, no bubbles, wrinkling, delamination,cracking, and other phenomena | — | Ga478-2004 |
Self viscosity | No loosening for 24 hours | — | Ga478-2004 |
Oxygen index |
≥32 |
% | GB/T 2046.2-2009 |
Flame retardant grade | V-0 | — | UL94-2015 |
Halogen content |
The contents of bromine and chlorine are less than those of 900 ppm, respectively. The total content of bromine + chlorine is less than 1500ppm |
— | EN14582:2016 |
Smoke density grade | ≤15 | — | GB/T 8627-2007 |
Data in the table represent average test results and are not to be used for specification purposes. The product user should make his l her own tests to determine the product.it's suitable for the intended use. |
PRODUCT General specifications
STANDARD SIZES: | ||
Width |
Length |
Thickness |
60mm |
5m | 0.7mm |
Other sizes and cores are available. Contact factory |
PRODUCT DISPLAY